Lunis R®, downlight for circular lamp | with various central modules
Version with single battery emergency light element | central module with coated cover plate
Lunis R® downlight for ceiling surface mounting or suspended mounting, consisting of circular downlight and central module | Circular downlight: with highly specular reflector for accommodating optical enclosure or louvre; choice of direct/indirect distribution, direct distribution via stray light baffle or direct distribution with coloured indirect component via colour filter segments | with ECG, additionally with single battery emergency light element | housing and reflector of aluminium, housing metallic grey (RAL 9006) or pure white (RAL 9010) | Central module: with perforated sheet steel cover, colour identical to downlight housing
Protection rating: IP20 Insulation class: I (without optical enclosure for circular downlight)
Electrical
Luminaire wired ready for connection, with 4-pole connection terminal (3-pole for normal mains with switched phase* + single pole for additional unswitched phase* for emergency light element), max. 2.5mm² | with ECG, with single battery emergency light element* (for 1h operation) and with LED (for optical self-test functioning control of battery**)
Rated voltage = 220…240V / AC 50…60Hz
* the switched phase (terminal >L1<) and the unswitched phase (terminal >L2<) must have the same phase angle | the emergency light battery is charged over the unswitched phase and the luminaire is informed of the operational condition (normal or emergency): - non-switched phase in operation: ---> normal operation (luminaire operation via mains, normal on/off switching)
- non-switched phase missing: ---> emergency operation (via battery) | luminaire is switched on even when luminaire was switched off in normal operation
** LED signals: Green LED: battery connected and charged Green blinking LED: battery being charged Red blinking LED: battery not connected or defect Yellow blinking LED: automatic discharging / charging of battery
Emergency operation with reduced lumen output: Lumen output phi=17% (T16-R 40W lamp) Lumen output phi=17% (T16-R 55W lamp)
permissible ambient temperature for luminaire with single battery emergency light element: 0°C…25°C
|