luminaire insert for T26 lamps, open distribution | reflector | IP20
Version luminaire insert | with single battery emergency light element
DUS® IP20 luminaire insert for mounting to DUS® trunking rail | can be positioned in module size 307mm* | open distribution** | with ECG, additionally with single battery emergency light element | sheet steel housing, silver (similar to RAL 9006) or pure white (similar to RAL 9010); twist lock catches with metal clips for rapid fixing to trunking rail
Protection rating: IP20 Insulation class: I * system size: 1 system unit (1SE) = 307mm ** extensive range of optical accessories Electrical
Luminaire insert for operation on normal mains or via the integral separate battery supply | wired ready for connection with 4-pole connection system for connection (3-pole for normal mains with switched phase*** + 1-pole for additional unswitched phase*** for emergency light element) | with ECG, with self-contained supply (for 1 hour operation) and with LED (for optical self-test functioning control of battery****) Version: 5LJ9....ED01 suitable for 5 or 7-core wired trunking rail; with phase preselection for 'normal supply' (on cores >L1< and >L2< of rail wiring) via moving of contact pin prior to installation in rail; >L3< for non-switched phase Version: 5LJ9....ED41 suitable for 7-core wired trunking rail; with phase preselection for 'normal supply' (on cores >L1<, >L2< and >L3< of rail wiring) via moving of contact pin prior to installation in rail; contact >4< for non-switched phase
UN= 220…240V / AC 50…60Hz
*** the switched phase (mains supply) and the unswitched phase must have the same phase angle | the emergency battery is charged via the non-switched phase and the luminaire is informed of the operational condition (mains or emergency operation): - non-switched phase in operation: ---> normal operation (luminaire operation via mains, normal on/off switching)
- non-switched phase missing: ---> emergency operation (via battery) | luminaire insert is switched on even when luminaire was switched off in normal operation
**** LED signals: Green LED: battery connected and charged Green blinking LED: battery being charged Red blinking LED: battery not connected or defect Yellow blinking LED: automatic discharging / charging of battery
Emergency operation with reduced lumen output: Lumen output phi=12% (T26 lamping, 58W) With 2-lamp luminaire inserts: operation with one lamp
Permissible ambient temperature for luminaire insert with single battery emergency light element: 0°C…25°C
|